Name : Medium Voltage cables
Conductor : Copper or aluminium, round, multiwire stranded and compact, according to VDE 0295.
Use : construction and power distribution industries
Air temperature : 30°C
voltage rating : 6/10kV
standards : - VDE 0276-620 - HD 620 - DIN EN 60228 Class 2
Place of Origin : Guangzhou, China
Brand Name : SUNWIN
Certification : ISO9001, ISO14001, OHSAS18001
MOQ : Negotiable
Price : Negotiable
Packaging Details : 100 m / tied, or customized
Delivery Time : 10 day
Payment Terms : 30% deposit, the balance is settled on the delivery date
Supply Ability : 100,000 m / month
6kV / 10kV Medium Voltage 2 Phase Cable Xlpe Insulated Wire Fire Resistant
medium voltage networks. This type of insulation is very chemically resistant and also resistant to cold. Due to various advantages, the XLPE-insulated type has vastly displaced the traditional classical paper-insulated types in many sectors.
In order to prevent the penetration of moisture and also to extend the duration of life, the XLPE-insulated
medium voltage cables are designed with longitudinally water-proof screen including an additional swell tape and a PE outer sheath.
The manufacture of this sheath is based on high density polyethylene (HDPE), in which an additive organic peroxide is mixed. Due to the heating and pressure the molecule chains are joined to each other, assuring the transition from thermoplastic to elastic condition.
In comparison to PVC and paper-insulated cables, the advantage of XLPE-insulated medium voltage power cables is that they possess a low dielectric factor, such as it is 100 times smaller than of PVC-insulated cables.
Moreover, a better dielectric constant value has an effect on the low mutual capacitance, the short-circuit to ground and the charging current of XLPE-insulated cables.
The good properties of XLPE-insulated cables remain constant through a wide temperature range.
Characteristics of XLPE
damage by sea up to +130°C
Conductor
Inner semi-conducting layer
Insulation
12/20 kV = 5,5 mm
18/30 kV = 8,0 mm
Outer semi-conducting layer
Concentricity of conductor
Semi-conducting type
Screen
Separator
Outer sheath
for 1x 500 mm2 /30 kV = 2,6 mm
Laying of Cable
In order to avoid any damage, the XLPE-insulated medium voltage cables should carefully laid and installed. It must be ensured that the cables should not be pulled over the hard or sharp edges.
The cable ends must be water-tight-sealed. After cutting the length both ends must be sealed immediately.
A laying depth of 60 to 80 cm is recommended. Single conductor cables are normally arranged in a trefoil touching or triangular shape.
For laying in conduits, the influence of thermal insulation of air space between the cable and the inner wall of conduit should be specially considered. The inner diameter of the conduit should be at least 1,5 times that of the diameter of the cable.
Bending radius
During the laying of XLPE cables, the bending radius should not be below of the following values:
Temperature range
During the installation, the temperature should not be below the following values:
Max. permissible tensile strength
By pulling the conductors with a pulling head (not for armoured cables)
P = No. of cores x conductor cross-section x o
o = permissible pulling tension N/mm2
– For Cu-conductor: 50 N/mm2
– For Alu-conductor: 30 N/mm2
Current carrying capacity
according to VDE 0276 part 620 or HD 620 S2
Laying in earth (ground)
in the laying depth 20°C
Laying in air
Laying in conduits
Cables for conduit systems laying in earth, a reduction of the current carrying capacity with a factor of
0,85 is recommended.
Test voltages
Kind of voltage test | Voltage test in kV | ||
U0/U = 6/10 kV |
U0/U = 12/20 kV |
U0/U = 18/30 kV | |
Voltage test a. c. in kV | 15 | 30 | 45 |
Voltage test d. c. in kV | 48 | 96 | 144 |
Voltage test a. c. (voltage test = 1000 h) | 18 | 36 | 54 |
Voltage test to cable system
During the operation or after laying the medium voltage power cables, the dielectric can be tested with
alternating or direct current. The test duration continues 30 minutes.
Kind of voltage test |
U0/U = 6/10 kV |
U0/U = 12/20 kV |
U0/U = 18/30 kV |
Voltage test a. c. in kV |
12 |
24 |
36 |
Voltage test d. c. in kV |
34 up to 48 |
67 up to 96 |
76 up to 108 |
![]() |