Conductor : bare copper conductor, fine wired stranded, class 5
Application : electric-installation tubes
Nominal voltage : Uο/U = 450/750 V
Insulation : PVC compound TI1 acc. to IEC 60227-3 / HD 21.3 S3 / DIN VDE 00281 part 3
Test voltage : 2500 V
Standards : HRN HD 21.3 S3 IEC 60227-3 DIN VDE 0281 part 3
Place of Origin : Guangzhou, China
Brand Name : SUNWIN
Certification : ISO9001, ISO14001, OHSAS18001
MOQ : Negotiable
Price : Negotiable
Packaging Details : 100 m / tied, or customized
Delivery Time : 10 day
Payment Terms : 30% deposit, the balance is settled on the delivery date
Supply Ability : 100,000 m / month
Color Customized Insulated Electrical Wire Non Sheated Single Core Cable
Application
Flexible insulated conductor used for laying in electric-installation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment, same as for protective laying for lighting of nominal voltage up to 1000 V alternating current, or up to 750 V direct current against earth.
Standards
HRN HD 21.3 S3
IEC 60227-3
DIN VDE 0281 part 3
Construction
Conductor: | bare copper conductor, fine wired stranded, class 5. acc. to IEC 60228 / HD 383 / DIN VDE 0295 | |
Insulation: | PVC compound TI1 acc. to IEC 60227-3 / HD 21.3 S3 / DIN VDE 00281 part 3 | |
Conductor colour identification: | acc. to IEC 60446 i.e. EN 60446 (corresponding to DIN VDE 0293) | |
possible insulation colours: | ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() | |
- yellow-green colour used only for protecting conductor, and green and yellow ones are permitted only if allowed by security regulations, i.e. if they can not get mixed up with the yellow-green conductor | ||
- blue colour is used for neutral conductor, black and brown are applied for alternating current phase conductors |
Temperature range:
during installation: | +5 °C up to +70 °C |
fixed installed: | -30 °C up to +70 °C |
at short circuit of max. 5 s: | up to 160 °C |
ambient temperature at storage: | up to 40 °C |
Nominal voltage: | Uο/U = 450/750 V |
Test voltage: | 2500 V |
Minimal inner bending radius: | 4D for D < 8 mm 5D for 8 - 12 mm 6D for D > 12 mm |
Behaviour in fire: | IEC 60332-1 |
Dimensions – conductor cross-section | Construction of individual conductor | External diameter | Insulation thickness | Conductor resistance at 20 °C | Specific. el. resistance of insulation at 70°C | Cu weight | Cable weight | Packing* |
nominal | min-max. | nominal | max | min. | approx. | |||
mm² | n x mm | mm | mm | Ω/km | MΩkm | kg/km | kg/km | |
1,5 | 30 x 0,25 | 2,8 - 03,4 | 0,7 | 13,3 | 0,0100 | 14,4 | 20 | c.100, c.200 |
2,5 | 50 x 0,25 | 3,4 - 04,1 | 0,8 | 7,98 | 0,0095 | 24,0 | 32 | c.100 |
4 | 56 x 0,30 | 3,9 - 04,8 | 0,8 | 4,95 | 0,0078 | 38,4 | 46 | c.100 |
6 | 84 x 0,30 | 4,4 - 05,3 | 0,8 | 3,30 | 0,0068 | 57,6 | 65 | c.100 |
10 | 80 x 0,40 | 5,7 - 06,8 | 1,0 | 1,91 | 0,0065 | 96,0 | 115 | c.100 |
16 | 128 x 0,40 | 6,7 - 08,1 | 1,0 | 1,21 | 0,0053 | 153,6 | 170 | c.100 |
25 | 200 x 0,40 | 8,4 - 10,2 | 1,2 | 0,780 | 0,0050 | 240 | 260 | CUT |
35 | 280 x 0,40 | 9,7 - 11,7 | 1,2 | 0,554 | 0,0043 | 336 | 360 | CUT |
50 | 400 x 0,40 | 11,5 - 13,9 | 1,4 | 0,386 | 0,0042 | 480 | 515 | CUT |
70 | 356 x 0,50 | 13,2 - 16,0 | 1,4 | 0,272 | 0,0036 | 672 | 710 | CUT |
95 | 485 x 0,50 | 15,1 - 18,2 | 1,6 | 0,206 | 0,0036 | 912 | 940 | CUT |
120 | 614 x 0,50 | 16,7 - 20,2 | 1,6 | 0,161 | 0,0032 | 1152 | 1180 | CUT |
150 | 765 x 0,50 | 18,6 - 22,5 | 1,8 | 0,129 | 0,0032 | 1440 | 1600 | CUT |
185 | 944 x 0,50 | 20,6 - 24,9 | 2,0 | 0,106 | 0,0032 | 1776 | 2100 | CUT |
240 | 1225 x 0,50 | 23,5 - 28,4 | 2,2 | 0,0801 | 0,0031 | 2304 | 3015 | CUT |
*) Packing: c.100 = coil 100 m, c.200 = coil 200 m CUT= cable in different lengths on drum or reel, possible cutting at required length
![]() |